EC fans2026-10-02T10:22:01+02:00

EC fans: a retrofit for a more energy-efficient air handling unit

We replace the belt-driven centrifugal fan in your existing air handling unit with direct-drive EC fans. The result: up to 30 percent lower energy costs, less maintenance and less noise, without having to remove the unit or the ductwork.

Retrofit

What are EC fans?

An EC fan, also known as an EC motor fan, is a fan with an electronically commutated motor. The motor is a brushless DC motor with permanent magnets, and built-in electronics control its speed. The impeller sits directly on the motor shaft, without a V-belt or pulleys. As a result, less energy is lost between the power socket and the airflow.

In an air handling unit, the fans are usually the largest consumers of electricity. EC motors achieve efficiencies of up to 90 percent and remain efficient at lower speeds. That is exactly how a unit runs most of the time: not at full power, but in line with the building’s demand.

EC fan or AC fan with a frequency inverter?

You can also make an existing AC fan speed-controlled by adding a frequency inverter. That is a realistic option. The difference lies in what happens between the motor and the airflow: in an AC fan, power is transmitted via a belt drive, and the inverter and the motor each have their own losses.

AC fan with frequency inverter compared with an EC fan
Aspect AC fan with frequency inverter EC fan
Drive V-belt and pulleys between motor and impeller Impeller mounted directly on the motor
Part-load efficiency Decreases as speed drops Remains high, even at low speed
Maintenance Tensioning and replacing belts, greasing bearings No belts, virtually maintenance-free
Contamination Belt wear particles enter the airflow No belt wear particles
Control Separate inverter, extra cabling and settings Built-in control, operated from the BMS

If the existing fan is fairly new, direct-drive and correctly sized, a frequency inverter may be the most cost-effective step. If an old belt-driven centrifugal fan is in place, an EC retrofit will deliver more in practice, because you eliminate belt losses and belt maintenance in one go.

The benefits of EC fans

  • Lower energy consumption. Up to 30 percent lower energy costs compared with a belt-driven centrifugal fan.
  • Less maintenance. No V-belts that wear, stretch and need replacing.
  • Reliable. With several smaller fans instead of one large one, the installation keeps running if one fails.
  • Less noise. Direct-drive EC fans run more quietly, which is noticeable in the rooms next to the plant room.
  • Works with any type of building management system. The built-in control can be operated directly.
  • Complies with the European ErP requirements for fans and air handling units.
  • Longer service life for the existing unit. You replace the part that wears, not the entire installation.
  • Possible tax benefit. In the Netherlands, EC retrofits may qualify for the Energy Investment Allowance (EIA).

What does an EC retrofit deliver and when does it pay for itself?

The savings come from two sources. The first is higher efficiency: fewer losses in the motor and drive. The second is controllability. A fan’s power consumption rises with the cube of its speed. A fan running at 80 percent of its speed draws roughly half the power. A unit that matches its airflow to the building’s demand therefore saves most during off-peak hours.

For the De Rotterdam project, we worked with Roodenburg Groep to replace the maintenance-intensive centrifugal fans in the air handling units with EC fans. The payback period came to approximately 1.8 years, with a significant CO2 reduction and lower maintenance costs. The units now meet the latest ErP requirements.

  • The number of operating hours per year: the more hours, the faster the payback
  • The type and age of the current fan and drive
  • The difference between the design airflow and what the building actually requires
  • The electricity price you pay
  • Whether other work on the unit, such as reconditioning, is carried out at the same time

In the Netherlands, EC retrofits may qualify for the Energy Investment Allowance (EIA). Whether this applies to your project depends on the current Energy List published by the Netherlands Enterprise Agency (RVO) and your tax situation. We provide the technical data you need for the application.

How does an EC fan retrofit work?

A retrofit fan is a new EC fan installed in the existing unit in place of the old centrifugal fan. It is comparable to replacing an incandescent bulb with an LED: the new one fits in the same place but uses much less energy. The unit, the coils and the ductwork stay in place.

  • Survey and measurement. We measure the current airflow, pressure and power consumption. This forms the baseline for the savings calculation.
  • Design. Based on the measurements, we select the number and type of EC fans, usually as a fan wall that fits within the existing fan section.
  • Planning. We work in phases and often outside office hours. Where necessary, we install temporary fans so the building remains ventilated.
  • Conversion. The old fan, motor and drive are removed, and the EC fans are installed and connected to the building management system.
  • Commissioning and follow-up measurement. We balance the airflow and measure again, so the savings are documented in black and white.

Fan wall: several small fans instead of one large one

With a fan wall, we replace one large fan with a wall of several smaller EC fans working side by side. If one fails, the others take over and the unit keeps running, which reduces the risk of complete failure to virtually zero. The smaller units also fit through a standard door and into a narrow plant room, so there is no need to open up walls or roofs to bring in a large fan.

Where are EC fans the best fit?

  • Offices and commercial buildings with long operating hours and an energy label requirement
  • Healthcare facilities and laboratories where ventilation runs day and night
  • Data centres, where reliability matters as much as energy consumption
  • Educational buildings with highly variable occupancy, where controllability counts
  • Industrial and production facilities with large air volumes

EC fans offshore

On production platforms, drilling rigs and vessels, HVAC units operate in harsh conditions: salt, moisture and large temperature fluctuations. Replacement there is expensive and logistically complex. That is why we combine reconditioning the HVAC unit with a retrofit to direct-drive EC fans, in a single planned shutdown. This extends the technical service life, lowers energy consumption and reduces noise in the accommodation.

Combining a retrofit with reconditioning and sustainability measures

If an air handling unit is being opened up anyway, that is the moment to do more than just the fan. Combining work means the unit is shut down once instead of several times, and the measures reinforce each other.

EC fans by AQ Group

For more than twenty years, AQ Group has specialised in cleaning, reconditioning and improving the sustainability of air handling units, both onshore and offshore. Because we know these units inside out, our survey immediately reveals any other issues besides the fan. Our own technicians carry out the retrofit, from measurement to commissioning.

  • Retrofits in offices, healthcare, data centres and offshore
  • Measurements before and after, with the savings documented
  • Certified to ISO 9001, ISO 14001, ISO 45001 and VCA**
  • Our own technicians, available nationwide and offshore

Frequently asked questions about EC fans

Will my air handling unit meet the ErP requirements after the retrofit?2026-10-01T16:54:03+02:00

As a rule, yes. The ErP regulation sets strict efficiency requirements for fans and air handling units. New units that comply are often larger and do not fit in the space of the old ones. With EC fans in your existing unit, you achieve today’s fan efficiencies without replacing the unit.

Is an EC retrofit also possible offshore?2026-10-01T16:54:03+02:00

Yes. On platforms and vessels, we usually combine the retrofit with reconditioning the HVAC unit, so everything is done in a single planned shutdown. The units are also protected against salt and moisture, and the accommodation becomes quieter thanks to the direct-drive fans.

What does an EC fan retrofit cost?2026-10-01T16:54:02+02:00

The price depends on the dimensions of the fan section, the number of fans, accessibility and the connection to the building management system. That is why we always start with a survey. As an indication of the return: for the De Rotterdam project, the payback period came to approximately 1.8 years.

Does the air handling unit have to be out of service for long during the retrofit?2026-10-01T16:54:02+02:00

No. We work in phases and preferably carry out the conversion outside office hours or at the weekend. Where the building cannot tolerate any downtime, we install temporary fans. In buildings with several units, we convert them one at a time so the rest keep running.

Do EC fans work with my building management system?2026-10-01T16:54:02+02:00

Yes. EC fans have built-in control that works with any type of building management system, for example via a 0–10 volt signal or a digital bus connection. The fan speed then automatically follows the building’s demand, for example based on CO2 levels or pressure.

Isn’t a frequency inverter on my existing fan cheaper?2026-10-01T16:54:02+02:00

Sometimes it is. If the fan is fairly new and direct-drive, a frequency inverter may be sufficient. With an older belt-driven centrifugal fan, however, the belt losses and maintenance remain even with an inverter. An EC retrofit eliminates both in one go. During the survey, we compare both options side by side.

Does an EC retrofit qualify for the EIA?2026-10-01T16:54:02+02:00

It may. In the Netherlands, the Energy Investment Allowance (EIA) applies to business assets included on the Energy List published by the Netherlands Enterprise Agency (RVO), and that list is updated every year. We provide the technical specifications that you or your adviser need to assess whether your project qualifies.

How much energy do EC fans save?2026-10-01T16:54:01+02:00

Compared with a belt-driven centrifugal fan, energy costs are up to 30 percent lower. The exact saving in your situation depends on the number of operating hours, the age of the current fan and how much of the time the unit runs at full load. Based on measurements taken beforehand, we calculate the savings for your unit.

Curious what a retrofit could deliver for your building?

We survey your air handling units, measure current consumption and calculate what an EC fan retrofit will deliver and when it will pay for itself. That gives you a well-founded business case before you make any decision.

Prefer to talk to us directly? Call +31 88 12 33 455 or email info@aqgroup.nl.